|
Most (95 - 98%) of the cold generation
for air-conditioning of buildings is done by (electric driven) compression
cooling machines. Besides there are heat driven absorption cooling machines.
Also sometimes heat pumps - mainly used for the generation of heat -
are used for the generation of cold.
Water chiller with compression cooling
The most occurring form of cold generation
for the air-conditioning of buildings takes place with a so-called water
chiller. Normally this is an electrical driven compression cooling machine
that delivers cold water.
The compressor is one of the six essential
parts of the compression-cooling machine. The others include the condenser,
evaporator, and expansion device. The compressor circulates refrigerant
through the system in a continuous cycle. From the evaporator the refrigerant
vapor is sucked on and brought to a higher pressure by compression.
Then the refrigerant vapor is transported to the condenser where it
condenses into liquid and whereby heat is given of. After that, in the
expansion device a reduction in pressure takes place, whereafter the
liquid at this lower pressure evaporates in the evaporator. Herewith
heat is withdrawn from water (water chiller) or air (DX-system), or
in other words cold is generated.
The coefficient of performance (COP) of
a cooling machine is the capacity [W] (the rate of heat removal by the
refrigerant) divided by the input power to the motor [W]. So cooling
machines with a higher COP are more efficient, than cooling machines
with a lower COP. COPs and capacity ranges are:
- Reciprocating compressors COP = 2,0
- 4,7 Cooling capacity 10 - 500 [kW]
- Screw compressors COP = 2,0 - 7,0 Cooling
capacity 300 - 2.000 [kW]
- Centrifugal compressors COP = 4,0 -
8,0 Cooling capacity 300 - 30.000 [kW]
|